AC Not Cooling and Running Too Much

House

7/29/2026 – Today Caleb with Estes checked for leaks after adding 2 lbs. of Freon last night. My calendar entry of today’s findings is below. As we have years of warranty on the coil (no warranty now on the $1800 labor) we will watch and see how it does. He said to call him if there is a problem.


Caleb/Estes: Pressures held but sniffer had a low reading at inside coil: maybe a microscopic leak in inside coil.

The process he told me he went through was:

  1. Trapped all the freon in the compressor, which raised the pressure there very high. No pressure loss, so no leaks there.
  2. Put nitrogen-with a little Freon left- in the lines and the inside coil up to 510 PSI. Saw a 1 PSI drop initially then steady for 30 minutes. If there is a leak, then very very small. Asked how many times the system has been checked, as if it was not fully charged when installed, then each check was a freon loss, and maybe that added up. He then came inside.
  3. He showed me his sniffer with a 17 ppm reading showing a very small detection inside the inside coil. Said that if the inside coil is leaking he usually gets readings in the 700s.
  4. As we have years of warranty on the coil (no warranty now on the $1800 labor) we will watch and see how it does. He said to call him if there is a problem.
  5. He pointed out we have a Carrier Infinity and that is a very good unit.